9,3/10 out of 1126 reviews
SCHNEIDER

module XPSAC - Emergency stop - 230 V AC - XPSAC3721

XPSAC3721

€78.09 Excl. Tax
€93.71 Inc. Tax
available In stock more than 25 units – Dispatched within 24/48h
  • check2 Technical support and dedicated single point of contact
  • check2 Free delivery from 100€ of purchase (Metropolitan France)
  • check2 100% secure payments maestro mastercard paypal visa payplug fintecture alma
Technical informations
Range of product: Preventa Safety automation
Product or component type: Preventa safety module
Safety module name: XPSAC
Safety module application: For emergency stop and switch monitoring
Function of module: Emergency stopSwitch monitoring
Safety level: Can reach PL e/category 4 conforming to EN/ISO 13849-1Can reach SILCL 3 conforming to EN/IEC 62061
Safety reliability data: MTTFd = 210.4 years conforming to EN/ISO 13849-1DC > 99 % conforming to EN/ISO 13849-1PFHd = 3.56E-9 1/h conforming to EN/IEC 62061
Type of start: Unmonitored
Connections - terminals: Captive screw clamp terminals, 1 x 0.14...1 x 2.5 mm² flexible with cable end, with double bezelCaptive screw clamp terminals, 1 x 0.14...1 x 2.5 mm² solid with cable end, with double bezelCaptive screw clamp terminals, 1 x 0.25...1 x 1.5 mm² flexible with cable end, with double bezelCaptive screw clamp terminals, 1 x 0.25...1 x 2.5 mm² flexible with cable end, with double bezelCaptive screw clamp terminals, 2 x 0.14...2 x 0.75 mm² flexible with cable end, with double bezelCaptive screw clamp terminals, 2 x 0.14...2 x 0.75 mm² solid with cable end, with double bezelCaptive screw clamp terminals, 2 x 0.25...2 x 1 mm² flexible with cable end, with double bezelCaptive screw clamp terminals, 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel
Output type: Relay instantaneous opening, 3 NO circuit(s), volt-free
Number of additional circuits: 1 solid state output
[Us] rated supply voltage: 230 V AC - 15...10 %
Supply frequency: 50/60 Hz
Maximum power consumption in VA: 6 VA AC
[Uc] control circuit voltage: 230 V
Breaking capacity: 180 VA holding AC-15 C300 relay output1800 VA inrush AC-15 C300 relay output
Breaking capacity: 1.5 A at 24 V (DC-13) time constant: 50 ms for relay output
Output thermal current: 6 A per relay for relay output
[Ith] conventional free air thermal current: 10.5 A
Associated fuse rating: 4 A gG or gL for relay output conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 2006 A fast blow for relay output conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200
Minimum output current: 10 mA for relay output
Minimum output voltage: 16 V for relay output
Maximum response time on input open: 100 ms
[Ui] rated insulation voltage: 300 V (pollution degree 2) conforming to IEC 60947-5-1300 V (pollution degree 2) conforming to DIN VDE 0110 part 1
[Uimp] rated impulse withstand voltage: 4 kV overvoltage category III conforming to IEC 60947-5-14 kV overvoltage category III conforming to DIN VDE 0110 part 1
Local signalling: 2 LEDs
Current consumption: 25 mA at 230 V AC on power supply
Mounting support: 35 mm symmetrical DIN rail
Product weight: 0.21 kg