Fast delivery - Satisfied or refunded for 14 days
9,3/10 out of 1126 reviews
⚠️ EXCEPTIONAL CLOSURE: No shipments from May 8th to 12th! Shipments will resume on May 13th ⚠️
SCHNEIDER

circuit breaker basic frame, ComPact NS 1600N, 50 kA at 415 VAC, 1600 A, fixed, manually operated, without trip unit, 3 P - 33260

33260

Obsolete product, here is the proposed substitution for the reference 33260 : C160N3FM
Technical informations
Range: ComPact
Range of product: ComPact NS630b...1600
Product name: ComPact NS
Device short name: Compact NS1600N
Product or component type: Basic frame
Device application: Distribution
Circuit breaker name: Compact NS1600N
Poles description: 3P
[In] rated current: 1600 A at 50 °C
[Ue] rated operational voltage: 690 V AC 50/60 Hz
Network type: AC
Network frequency: 50/60 Hz
Suitability for isolation: Yes conforming to EN/IEC 60947-2
Utilisation category: Category B
Breaking capacity: 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-285 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-250 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-250 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-240 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity code: N 50 kA 415 V AC
Control type: ToggleRotary handle
Mounting mode: Fixed
[Ui] rated insulation voltage: 800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage: 8 kV conforming to IEC 60947-2
[Ics] rated service breaking capacity: 30 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)22 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)37 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)37 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)37 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)
[Icw] rated short-time withstand current: 19.2 kA 1 s conforming to IEC 60947-2
Integral instant protection: 40 kA
Mechanical durability: 10000 cycles conforming to IEC 60947-2
Electrical durability: 5000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-21000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-22000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-22000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Power losses: 74 W
Mounting support: Backplate
Connection pitch: 70 mm
Protection type: Without protection
Height: 327 mm
Width: 210 mm
Depth: 147 mm
Compatibility code: NS1600
In short
Reference 33260
Product Name circuit breaker basic frame, ComPact NS 1600N, 50 kA at 415 VAC, 1600 A, fixed, manually operated, without trip unit, 3 P - 33260
Device function Distribution
Related Categories