9,3/10 out of 1126 reviews
SCHNEIDER

TeSys D contactor - 4P(2 NO + 2 NC) - AC-1 <= 440 V 60 A 110 V AC 50/60 Hz coil - LC1D400086F7

LC1D400086F7

€210.42 Excl. Tax
€252.50 Inc. Tax
preorder Supply in process – Average delivery time 4/6 weeks
  • check2 Technical support and dedicated single point of contact
  • check2 Free delivery from 100€ of purchase (Metropolitan France)
  • check2 100% secure payments maestro mastercard paypal visa payplug fintecture alma
Technical informations
Range of product: TeSys D
Range: TeSys
Product name: TeSys D
Product or component type: Contactor
Device short name: LC1D
Contactor application: Resistive load
Utilisation category: AC-1
Poles description: 4P
Pole contact composition: 2 NO + 2 NC
[Ue] rated operational voltage: Power circuit: Power circuit:
[Ie] rated operational current: 60 A (at
Control circuit type: AC at 50/60 Hz
[Uc] control circuit voltage: 110 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947
Overvoltage category: III
[Ith] conventional free air thermal current: 60 A (at 60 °C) for power circuit
Irms rated making capacity: 800 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity: 800 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current: 320 A 40 °C - 10 s for power circuit720 A 40 °C - 1 s for power circuit72 A 40 °C - 10 min for power circuit165 A 40 °C - 1 min for power circuit
Associated fuse rating: 80 A gG at 80 A gG at
Average impedance: 1.5 mOhm - Ith 60 A 50 Hz for power circuit
[Ui] rated insulation voltage: Power circuit: 600 V CSA certifiedPower circuit: 600 V UL certifiedPower circuit: 690 V conforming to IEC 60947-4-1
Electrical durability: 1.4 Mcycles 60 A AC-1 at Ue
Power dissipation per pole: 5.4 W AC-1
Protective cover: Without
Mounting support: PlateRail
Standards: CSA C22.2 No 14EN 60947-4-1EN 60947-5-1IEC 60947-4-1IEC 60947-5-1UL 508
Product certifications: DNVLROS (Lloyds register of shipping)GLRINACCCBVULGOSTCSA
Connections - terminals: Control circuit: lugs-ring terminals (external diameter: 8 mm) Power circuit: lugs-ring terminals (external diameter: 16.5 mm)
Tightening torque: Control circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5Control circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5Power circuit: 6 N.m - on lugs-ring terminals hexagonal screw head 10 mm M6
Operating time: 4...19 ms opening12...26 ms closing
Safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability: 6 Mcycles
Maximum operating rate: 3600 cyc/h 60 °C
Coil technology: Without built-in suppressor module
Control circuit voltage limits: 0.3...0.6 Uc (-40...70 °C):drop-out AC 50/60 Hz0.8...1.1 Uc (-40...60 °C):operational AC 50 Hz0.85...1.1 Uc (-40...60 °C):operational AC 60 Hz1...1.1 Uc (60...70 °C):operational AC 50/60 Hz
Inrush power in VA: 140 VA 60 Hz cos phi 0.75 (at 20 °C)160 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in VA: 13 VA 60 Hz cos phi 0.3 (at 20 °C)15 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation: 4...5 W at 50/60 Hz
Contact compatibility: M1
Compatibility code: LC1D
In short
Reference LC1D400086F7
Product Name TeSys D contactor - 4P(2 NO + 2 NC) - AC-1 <= 440 V 60 A 110 V AC 50/60 Hz coil - LC1D400086F7
Range TeSys
Related Categories