9,3/10 out of 1126 reviews
SCHNEIDER

circuit breaker ComPact NSX160H, 70 kA at 415 VAC, TMD trip unit 63 A, 4 poles 4d - LV430694

LV430694

Obsolete product, here is the list of products to combine to replace the reference LV430694 :
  • C104TM063
  • C16H4
  • Technical informations
    Range: ComPact
    Product name: ComPact NSX
    Range of product: ComPact NSX100...250
    Device short name: NSXm 160H
    Product or component type: Circuit breaker
    Device application: Distribution
    Poles description: 4P
    Protected poles description: 4t
    Neutral position: Left
    [In] rated current: 63 A at 40 °C
    [Ue] rated operational voltage: 690 V AC 50/60 Hz
    Network type: AC
    Network frequency: 50/60 Hz
    Suitability for isolation: Yes conforming to EN/IEC 60947-2
    Utilisation category: Category A
    Breaking capacity: 10 kA at 600 V AC 50/60 Hz conforming to UL 50885 kA at 240 V AC 50/60 Hz conforming to UL 50865 kA at 480 V AC 50/60 Hz conforming to UL 50810 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-235 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-250 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-265 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-270 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
    Breaking capacity code: H 70 kA 415 V AC
    Trip unit name: TM-D
    Trip unit technology: Thermal-magnetic
    Trip unit protection functions: LI
    Control type: Toggle
    Mounting mode: Fixed
    [Ui] rated insulation voltage: 800 V AC 50/60 Hz
    [Uimp] rated impulse withstand voltage: 8 kV
    [Ics] rated service breaking capacity: 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-235 kA at 525 V AC 50/60 Hz conforming to IEC 60947-250 kA at 500 V AC 50/60 Hz conforming to IEC 60947-265 kA at 440 V AC 50/60 Hz conforming to IEC 60947-270 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
    Mechanical durability: 40000 cycles
    Electrical durability: 7500 cycles at 690 V In15000 cycles at 690 V In/220000 cycles at 440 V In40000 cycles at 440 V In/2
    Mounting support: Backplate
    Upside connection: Front
    Downside connection: Front
    Connection pitch: 35 mm
    Protection type: L
    Trip unit rating: 63 A at 40 °C
    Long time pick-up adjustment type Ir: Adjustable
    Long time pick-up adjustment range: 0.7...1 x In
    Long time delay adjustment type: Fixed
    [tr] long-time delay adjustment range: 120...400 s at 1.5 x In15 s at 6 x Ir
    Short-time pick-up adjustment type Isd: Fixed
    [Isd] short-time pick-up adjustment range: 500 A
    Short-time delay adjustment type: Fixed
    Earth-leakage protection: Without
    Neutral protection setting: 1 x Ir (4t)
    Number of slots: 5 slot(s)
    Width: 140 mm
    Height: 161 mm
    Depth: 86 mm
    Product weight: 2.6 kg
    Compatibility code: NSX160
    In short
    Reference LV430694
    Product Name circuit breaker ComPact NSX160H, 70 kA at 415 VAC, TMD trip unit 63 A, 4 poles 4d - LV430694
    Range Compact
    Device function Distribution
    Related Categories