9,3/10 out of 1126 reviews
SCHNEIDER

circuit breaker basic frame, ComPact NS 2000N, 50 kA at 415 VAC, 2000 A, fixed, manually operated, without trip unit, 4 P - 34009

34009

Obsolete product, here is the proposed substitution for the reference 34009 : C200N4FM
Technical informations
Range: ComPact
Range of product: ComPact NS1600b...3200
Product name: ComPact NS
Device short name: Compact NS2000N
Product or component type: Basic frame
Device application: Distribution
Circuit breaker name: Compact NS2000N
Poles description: 4P
Neutral position: Left
[In] rated current: 2000 A at 50 °C
[Ue] rated operational voltage: 690 V AC 50/60 Hz
Network type: AC
Network frequency: 50/60 Hz
Suitability for isolation: Yes conforming to EN/IEC 60947-2
Utilisation category: Category B
Breaking capacity: 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-265 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-270 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-265 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-265 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity code: N 50 kA 415 V AC
Control type: Toggle
Mounting mode: Fixed
[Ui] rated insulation voltage: 800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage: 8 kV conforming to IEC 60947-2
[Ics] rated service breaking capacity: 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)65 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)65 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)52 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)65 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)
[Icw] rated short-time withstand current: 32 kA 3 s conforming to IEC 60947-2
Integral instant protection: 130 kA
Mechanical durability: 5000 cycles conforming to IEC 60947-2
Electrical durability: 1000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-22000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-22000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-23000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Power losses: 84 W
Mounting support: Backplate
Upside connection: Front
Downside connection: Front
Connection pitch: 115 mm
Protection type: Without protection
Height: 350 mm
Width: 535 mm
Depth: 160 mm
Compatibility code: NS2000
In short
Reference 34009
Product Name circuit breaker basic frame, ComPact NS 2000N, 50 kA at 415 VAC, 2000 A, fixed, manually operated, without trip unit, 4 P - 34009
Range NS1600b...3200
Device function Distribution
Related Categories