Technical informations
Range: TeSys
Range of product: TeSys U
Product name: TeSys U
Device short name: LUCB
Product or component type: Advanced control unit
Device application: Motor controlMotor protection
Product specific application: Basic protection and advanced functions, communication
Function available: Protection against phase failure and phase imbalanceManual resetEarth fault protectionProtection against overload and short-circuit
Product compatibility: Power base LUB32Power base LUB38Power base LUB320Power base LUB380Reversing contactor breaker LU2B32FUReversing contactor breaker LU2B38FU
[Ue] rated operational voltage: 690 V AC
Network frequency: 40...60 Hz
Load type: 3-phase motor - cooling: self-cooled
Utilisation category: AC-43AC-44AC-41
Motor power kW: 7.5 kW at 400...440 V AC 50/60 Hz9 kW at 500 V AC 50/60 Hz15 kW at 690 V AC 50/60 Hz
Thermal protection adjustment range: 4.5...18 A
Thermal overload class: Class 10 - frequency limit: 40...60 Hz - temperature compensation: -25...70 °C conforming to IEC 60947-6-2Class 10 - frequency limit: 40...60 Hz - temperature compensation: -25...70 °C conforming to UL 508
Tripping threshold: 14.2 x Ir +/- 20 %
Phase failure sensitivity: Yes
[Uc] control circuit voltage: 110...240 V AC110...220 V DC
Control circuit voltage limits: 88...264 V for AC circuit 110...240 V in operation88...242 V for DC circuit 110...220 V in operation55 V for AC circuit 110...240 V drop-out55 V for DC circuit 110...220 V drop-out
Typical current consumption: 280 mA at 110...240 V AC I maximum while closing with LUB32280 mA at 110...240 V AC I maximum while closing with LUB38280 mA at 110...220 V DC I maximum while closing with LUB32280 mA at 110...220 V DC I maximum while closing with LUB3825 mA at 110...240 V AC I rms sealed with LUB3225 mA at 110...240 V AC I rms sealed with LUB3825 mA at 110...220 V DC I rms sealed with LUB3225 mA at 110...220 V DC I rms sealed with LUB38
Heat dissipation: 3 W for control circuit with LUB323 W for control circuit with LUB38
Operating time: 35 ms opening with LUB32 for control circuit35 ms opening with LUB38 for control circuit50 ms closing with LUB32 for control circuit50 ms closing with LUB38 for control circuit
Reset: Manual reset
Standards: EN 60947-6-2IEC 60947-6-2UL 60947-4-1, with phase barrierCSA C22.2 No 60947-4-1, with phase barrier
Product certifications: CEULCSACCCEACASEFAATEXMarine
[Ui] rated insulation voltage: 690 V conforming to IEC 60947-6-2600 V conforming to UL 60947-4-1600 V conforming to CSA C22.2 No 60947-4-1
[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947-6-2
Safe separation of circuit: 400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1