Technical informations
Range of product: TeSys D
Range: TeSys
Product or component type: Contactor
Device short name: LC1D
Contactor application: Motor controlResistive load
Utilisation category: AC-3AC-4AC-1AC-2AC-3e
Control circuit type: AC at 50/60 Hz
Poles description: 3P
Pole contact composition: 3 NO
[Ie] rated operational current: 80 A (at 65 A (at 65 A (at
Motor power kW: 30 kW at 440 V AC 50 Hz (AC-3)11 kW at 400 V AC 50 Hz (AC-4)30 kW at 380...400 V AC 50 Hz (AC-3)37 kW at 500 V AC 50 Hz (AC-3)37 kW at 660...690 V AC 50 Hz (AC-3)18.5 kW at 220...230 V AC 50 Hz (AC-3)30 kW at 415 V AC 50 Hz (AC-3)37 kW at 1000 V AC 50 Hz (AC-3)30 kW at 440 V AC 50 Hz (AC-3e)30 kW at 380...400 V AC 50 Hz (AC-3e)37 kW at 500 V AC 50 Hz (AC-3e)37 kW at 660...690 V AC 50 Hz (AC-3e)18.5 kW at 220...230 V AC 50 Hz (AC-3e)30 kW at 415 V AC 50 Hz (AC-3e)37 kW at 1000 V AC 50 Hz (AC-3e)
Coil technology: Without built-in bidirectional peak limiting diode suppressor
Protective cover: With
Motor power hp: 5 hp at 115 V AC 60 Hz for 1 phase motors10 hp at 230/240 V AC 60 Hz for 1 phase motors20 hp at 200/208 V AC 60 Hz for 3 phases motors20 hp at 230/240 V AC 60 Hz for 3 phases motors40 hp at 460/480 V AC 60 Hz for 3 phases motors50 hp at 575/600 V AC 60 Hz for 3 phases motors
Auxiliary contacts type: type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1
Auxiliary contact composition: 1 NO + 1 NC
[Uc] control circuit voltage: 24 V AC 50/60 Hz
Control circuit voltage limits: 0.3...0.6 Uc (-40...70 °C):drop-out AC 50/60 Hz0.8...1.1 Uc (-40...60 °C):operational AC 50 Hz0.85...1.1 Uc (-40...60 °C):operational AC 60 Hz1...1.1 Uc (60...70 °C):operational AC 50/60 Hz
[Ui] rated insulation voltage: Control circuit: 600 V CSA certifiedControl circuit: 600 V UL certifiedPower circuit: 600 V CSA certifiedPower circuit: 600 V UL certifiedControl circuit: 690 V conforming to IEC 60947-1Power circuit: 690 V conforming to IEC 60947-1
[Uimp] rated impulse withstand voltage: 8 kV conforming to IEC 60947
Overvoltage category: III
Mounting support: PlateRail
Flame retardance: V1 conforming to UL 94
Connections - terminals: Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²rigidControl circuit: screw clamp terminals 2 cable(s) 1...4 mm²rigidControl circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable endControl circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable endControl circuit: screw clamp terminals 1 cable(s) 1...2.5 mm²flexible with cable endControl circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable endPower circuit: screw terminals 1 cable(s) 2.5...25 mm²rigidPower circuit: screw terminals 2 cable(s) 2.5...16 mm²rigidPower circuit: screw terminals 1 cable(s) 2.5...25 mm²flexible without cable endPower circuit: screw terminals 2 cable(s) 2.5...16 mm²flexible without cable endPower circuit: screw terminals 1 cable(s) 2.5...25 mm²flexible with cable endPower circuit: screw terminals 2 cable(s) 2.5...10 mm²flexible with cable end
Tightening torque: Control circuit: 1.7 N.m - on screw clamp terminal - with screwdriver flat Ø 6 mmControl circuit: 1.7 N.m - on screw clamp terminal - with screwdriver Philips No 2Power circuit: 5 N.m - on screw terminal - with screwdriver flat Ø 6 to Ø 8 mm
[Ue] rated operational voltage: Power circuit:
[Ith] conventional free air thermal current: 10 A (at 60 °C) for control circuit80 A (at 60 °C) for power circuit
Irms rated making capacity: 1000 A at 440 V for power circuit conforming to IEC 60947140 A AC for control circuit conforming to IEC 60947-5-1
Rated breaking capacity: 1000 A at 440 V for power circuit conforming to IEC 60947
Associated fuse rating: 10 A gG for control circuit conforming to IEC 60947-5-1125 A gG at 160 A gG at
Power dissipation per pole: 4.2 W AC-36.4 W AC-14.2 W AC-3e
Inrush power in VA: 140 VA cos phi 0.75 (at 20 °C)160 VA cos phi 0.75 (at 20 °C)
Hold-in power consumption in VA: 13 VA 60 Hz cos phi 0.3 (at 20 °C)15 VA 50 Hz cos phi 0.3 (at 20 °C)
Operating time: 4...19 ms opening12...26 ms closing
Safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability: 6000000 cycles
Maximum operating rate: 3600 cyc/h 60 °C
Minimum switching current: 5 mA for control circuit
Minimum switching voltage: 17 V for control circuit
Non-overlap time: 1.5 ms on de-energisation between NC and NO contacts1.5 ms on energisation between NC and NO contacts
Insulation resistance: > 10 MOhm for control circuit