9,3/10 out of 1126 reviews
SCHNEIDER

TeSys GV7 - circuit breaker - 3P - AC-3 - 90...150 A - thermal-magnetic - GV7RE150

GV7RE150

Obsolete product, here is the proposed substitution for the reference GV7RE150 : GV5P150F
Technical informations
Range: TeSys
Range of product: TeSys GV7
Product name: TeSys GV7
Product or component type: Circuit breaker
Device short name: GV7R
Device application: Motor
Poles description: 3P
Network type: AC
Utilisation category: AC-3 conforming to IEC 60947-4-1
Network frequency: 50/60 Hz conforming to IEC 60947-4-1
Breaking capacity: 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-285 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-235 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-225 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-28 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity: 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2100 % at 220/240 V AC 50/60 Hz conforming to IEC 60947-2100 % at 380/415 V AC 50/60 Hz conforming to IEC 60947-250 % at 500 V AC 50/60 Hz conforming to IEC 60947-250 % at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Trip unit rating: 90...150 A
Trip unit technology: Thermal-magnetic
Mounting mode: By screwsBy clips
Mounting support: FlushRailPanel mountingKit for fixing the switchgear
Mounting position: Vertical
Motor power kW: 110 kW at 660...690 V AC 50/60 Hz55 kW at 400...415 V AC 50/60 Hz75 kW at 400...415 V AC 50/60 Hz75 kW at 500 V AC 50/60 Hz90 kW at 500 V AC 50/60 Hz90 kW at 660...690 V AC 50/60 Hz
Control type: Rocker lever
[In] rated current: 150 A
[Ue] rated operational voltage: 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage: 750 V AC 50/60 Hz conforming to IEC 60947-2
[Ith] conventional free air thermal current: 150 A conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage: IEC 60947-2 8 kV
Power dissipation: 8.7 W
Power dissipation per pole: 8.7 W
Mechanical durability: 40000 cycles
Electrical durability: 20000 cycles for AC-3 at 440 V In40000 cycles for AC-3 at 440 V In/2
Maximum operating rate: 25 cyc/h
Rated duty: Continuous conforming to IEC 60947-4-1
Connection pitch: 35 mm without spreaders45 mm with spreaders
Connections - terminals: BarsCable with lug - external diameter: 10 mmScrewBare cable connectors 1.5...95 mm²
Tightening torque: 10 N.m on screw M6 screw type 15 N.m on bare cable connectors for cable 1.5...95 mm²
Mechanical robustness: Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-27Vibrations: 2.5 Gn, 0...25 Hz conforming to IEC 60068-2-6
Suitability for isolation: Yes conforming to IEC 60947-1
Phase failure sensitivity: Yes conforming to IEC 60947-4-1 § 7-2-1-5-2
Height: 161 mm
Width: 105 mm
Depth: 111 mm
Product weight: 2.02 kg
Compatibility code: GV7RE
In short
Reference GV7RE150
Product Name TeSys GV7 - circuit breaker - 3P - AC-3 - 90...150 A - thermal-magnetic - GV7RE150
Range TeSys
Device function Moteur
Related Categories