Fast delivery - Satisfied or refunded for 14 days
9,3/10 out of 1126 reviews
⚠️ EXCEPTIONAL CLOSURE: No shipments from May 8th to 12th! Shipments will resume on May 13th ⚠️
SCHNEIDER

TeSys GV4 - Auxiliary contact OF or SD for GV4 - GV4AE11

GV4AE11

€2.64 Excl. Tax
€3.17 Inc. Tax
preorder Supply in process – Average delivery time 4/6 weeks
  • check2 Technical support and dedicated single point of contact
  • check2 Free delivery from 100€ of purchase (Metropolitan France)
  • check2 100% secure payments maestro mastercard paypal visa payplug fintecture alma
Technical informations
Range: TeSys
Device short name: GV4AE
Product or component type: Auxiliary contact
Device application: Signalling
Range compatibility: TeSys GV4TeSys BV4
Auxiliary contact composition: 1 NO/NC
[Ue] rated operational voltage:
[Ith] conventional free air thermal current: 5 A conforming to IEC 60947-5-15 A conforming to CSA C22.2 No 145 A conforming to UL 508
Mounting mode: Internal mounting
[Ui] rated insulation voltage: 690 V conforming to IEC 60947-1
[Ie] rated operational current: 5 A 5 A 4 A 110/127 V AC-15 conforming to IEC 60947-5-13 A 220/240 V AC-15 conforming to IEC 60947-5-12.5 A 380...440 V AC-15 conforming to IEC 60947-5-10.11 A 660/690 V AC-15 conforming to IEC 60947-5-15 A 2.5 A 48 V DC-12 conforming to IEC 60947-5-10.6 A 110/127 V DC-12 conforming to IEC 60947-5-10.3 A 250 V DC-12 conforming to IEC 60947-5-12.5 A 1.2 A 48 V DC-12 conforming to IEC 60947-5-10.35 A 110/127 V DC-12 conforming to IEC 60947-5-10.05 A 250 V DC-12 conforming to IEC 60947-5-11 A 0.2 A 48 V DC-12 conforming to IEC 60947-5-10.05 A 110/127 V DC-12 conforming to IEC 60947-5-10.03 A 250 V DC-12 conforming to IEC 60947-5-1
Rated power in VA: 120 VA AC-12 at 24 V conforming to IEC 60947-5-1240 VA AC-12 at 48 V conforming to IEC 60947-5-1635 VA AC-12 at 110/127 V conforming to IEC 60947-5-11200 VA AC-12 at 230/240 V conforming to IEC 60947-5-12200 VA AC-12 at 380/440 V conforming to IEC 60947-5-13450 VA AC-12 at 660/690 V conforming to IEC 60947-5-1
Rated power in W: DC-12: 120 W 24 V conforming to IEC 60947-5-1DC-12: 120 W 48 V conforming to IEC 60947-5-1DC-12: 66 W 110 V conforming to IEC 60947-5-1DC-12: 75 W 250 V conforming to IEC 60947-5-1
Associated fuse rating: 5 A gG at 690 V conforming to IEC 60947-5-1
Minimum switching current: 2 mA
Minimum switching voltage: 17 V
Mechanical durability: 40000 cycles
Connections - terminals: Spring terminals 1 0.5...1.5 mm² - cable stiffness: flexible without cable end
Wire stripping length: 8 mm
In short
Reference GV4AE11
Product Name TeSys GV4 - Auxiliary contact OF or SD for GV4 - GV4AE11
Range TeSys
Device function Signalisation
Related Categories