Fast delivery - Satisfied or refunded for 14 days
9,3/10 out of 1126 reviews
⚠️ EXCEPTIONAL CLOSURE: No shipments from May 8th to 12th! Shipments will resume on May 13th ⚠️
SCHNEIDER

trip unit MicroLogic 6.2 EM for ComPacT NSX 250 circuit breakers, electronic, rating 220 A, 3 poles 3d - C2536M220

C2536M220

€675.45 Excl. Tax
€810.54 Inc. Tax
preorder Supply in process – Average delivery time 4/6 weeks
  • check2 Technical support and dedicated single point of contact
  • check2 Free delivery from 100€ of purchase (Metropolitan France)
  • check2 100% secure payments maestro mastercard paypal visa payplug fintecture alma
Technical informations
Range: ComPacT new generation
Range of product: ComPacT NSX100...250 new generation
Product or component type: Trip unit
Trip unit name: Micrologic 6.2 E-M
Trip unit technology: Electronic
Range compatibility: ComPacT new generation NSX250
Device application: Motor
Poles description: 3P
Protected poles description: 3D
Trip unit protection functions: LSIG
Protection type: L
[In] rated current: 220 A at 65 °C
[Ue] rated operational voltage: 690 V AC 50/60 Hz
Network type: AC
Network frequency: 50/60 Hz
Mounting mode: Fixed
Motor tripping class: 3051020
Complementary motor protection: UnderloadProtracted starting timeStalled rotorCurrent unbalance
Long time pick-up adjustment type Ir: Adjustable 9 settings
Long time pick-up adjustment range: 100...220 A
Long time delay adjustment type: Adjustable
[tr] long-time delay adjustment range: 120 s at 1.5 x Ir for trip class 56.5 s at 6 x Ir for trip class 55 s at 7.2 x Ir for trip class 5240 s at 1.5 x Ir for trip class 1013.5 s at 6 x Ir for trip class 1010 s at 7.2 x Ir for trip class 10480 s at 1.5 x Ir for trip class 2026 s at 6 x Ir for trip class 2020 s at 7.2 x Ir for trip class 20720 s at 1.5 x Ir for trip class 3038 s at 6 x Ir for trip class 3030 s at 7.2 x Ir for trip class 30
Thermal memory: 20 minutes before and after tripping
Short-time pick-up adjustment type Isd: Adjustable 9 settings
[Isd] short-time pick-up adjustment range: 5...13 x Ir
Short-time delay adjustment type: Fixed
Instantaneous pick-up adjustment type Ii: Fixed
Instantaneous pick-up adjustment range: 3300 A
Ground-fault pick-up adjustment type: Adjustable
[Ig] ground-fault pick-up adjustment range: 0.2...1 x InIg enable on/off
Ground-fault time delay adjustment type -tg: Adjustable
[tg] ground-fault time delay adjustment range: 0...0.4 s
Earth-leakage protection: Without
Zone selective interlocking ZSI: With
Local signalling: Flashing LED (green) for ready to operateLED 95 % Ith (red) for temperature over set point
Display type: LCD display
Type of measurement: Energy meter
Communication of data: Energy meteringProtection and alarm settingsTime-stamped histories and event tablesInstantaneous and demand valuesMaintenance indicatorsDemand current and powerPower qualityMaximeters/minimeters
Electrical data recording: Maintenance indicators
In short
Reference C2536M220
Product Name trip unit MicroLogic 6.2 EM for ComPacT NSX 250 circuit breakers, electronic, rating 220 A, 3 poles 3d - C2536M220
Range ComPacT nouvelle génération
Related Categories