Fast delivery - Satisfied or refunded for 14 days
9,3/10 out of 1126 reviews
⚠️ EXCEPTIONAL CLOSURE: No shipments from May 8th to 12th! Shipments will resume on May 13th ⚠️
SCHNEIDER

Residual current breaker with overcurrent protection (RCBO), Acti9 iCV40N, 3P+N, 40A, C curve, 6000A, A-SI type, 30mA - A9DF3740

A9DF3740

€175.50 Excl. Tax
€210.60 Inc. Tax
available In stock – Dispatched within 24/48h
  • check2 Technical support and dedicated single point of contact
  • check2 Free delivery from 100€ of purchase (Metropolitan France)
  • check2 100% secure payments maestro mastercard paypal visa payplug fintecture alma
Technical informations
Range: Acti9
Product name: Acti9 iCV40
Product or component type: Residual current breaker with overcurrent protection (RCBO)
Device short name: iCV40N
Device application: Distribution
Poles description: 3P + N
Number of protected poles: 3
Neutral position: Left
[In] rated current: 40 A
Network type: AC
Trip unit technology: Thermal-magnetic
Curve code: C
Earth-leakage sensitivity: 30 mA
Earth-leakage protection time delay: Instantaneous
Earth-leakage protection class: Type A-SI (Super Immunised)
Breaking capacity: 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 61009-2-1
Suitability for isolation: Yes conforming to EN/IEC 60947-2
Quality labels: VDEEAC
Device location in system: Outgoer
Network frequency: 50/60 Hz
[Ue] rated operational voltage: 400 V AC 50/60 Hz
Magnetic tripping limit: 5...10 x In
Residual current tripping technology: Voltage independent
[Ics] rated service breaking capacity: 6000 A 100 % x Icn at 400 V AC 50/60 Hz conforming to EN/IEC 61009-2-1
Rated breaking and making capacity: Idm 3000 A at 400 V AC 50/60 Hz conforming to EN/IEC 61009-2-1
Limitation class: 3 conforming to EN/IEC 61009-2-1
[Ui] rated insulation voltage: 440 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage: 4 kV
Contact position indicator: Yes
Control type: Toggle
Local signalling: Fault indicationON/OFF indication
Mounting mode: Clip-on
Mounting support: DIN rail
Comb busbar and distribution block compatibility: Top or bottom: tooth
Connection pitch: 18 mm between phases9 mm between phase and neutral
9 mm pitches: 10
Height: 93 mm
Width: 90 mm
Depth: 73 mm
Net weight: 500 g
Colour: White
Mechanical durability: 20000 cycles
Electrical durability: 10000 cycles
Locking options description: SealablePadlocking device
Connections - terminals: Tunnel type terminals top or bottom 1...16 mm² rigidTunnel type terminals top or bottom 1...10 mm² flexible
Wire stripping length: 14 mm for top or bottom connection
Tightening torque: 2 N.m top or bottom
Earth-leakage protection: Integrated
Market segment: Small commercial
Compatibility code: ICV40N
In short
Reference A9DF3740
Product Name Residual current breaker with overcurrent protection (RCBO), Acti9 iCV40N, 3P+N, 40A, C curve, 6000A, A-SI type, 30mA - A9DF3740
Range Acti9
Related Categories