calcActive())">
SCHNEIDER
trip unit MicroLogic 6.3 E for ComPacT NSX 400/630 circuit breakers, electronic, rating 400A, 4 poles 4d - C4046E400
C4046E400
€1,330.27 Excl. Tax
€1,596.32 Inc. Tax
Excl. Tax
Excl. Tax
Incl. Tax
Incl. Tax
You save
Supply in process - Average delivery time 4/6 weeks
- Technical support and dedicated single point of contact
- Free delivery from 250€ of purchase (Metropolitan France)
- 100% secure payments
Technical informations
| Range: | ComPacT new generation |
|---|---|
| Range of product: | ComPacT NSX400...630 new generation |
| Product or component type: | Trip unit |
| Trip unit name: | Micrologic 6.3 E |
| Trip unit technology: | Electronic |
| Range compatibility: | ComPacT new generation NSX400ComPacT new generation NSX630 |
| Device application: | Distribution |
| Poles description: | 4P |
| Protected poles description: | 3D + N/24D3D + OSN3D |
| Neutral position: | Left |
| Trip unit protection functions: | LSIG |
| Protection type: | L |
| [In] rated current: | 400 A at 40 °C |
| [Ue] rated operational voltage: | 690 V AC 50/60 Hz |
| Network type: | AC |
| Network frequency: | 50/60 Hz |
| Mounting mode: | Fixed |
| Long time pick-up adjustment type Ir: | Adjustable |
|---|---|
| Long time pick-up adjustment range: | 160...400 A |
| Long time delay adjustment type: | Adjustable |
| [tr] long-time delay adjustment range: | 15...400 s at 1.5 x Ir0.35...11 s at 7.2 x Ir0.5...16 s at 6 x Ir |
| Neutral protection setting: | 0.5 x Ir (3D + N/2)1 x Ir (4D)1.6 x Ir (3D + OSN)No protection (3D) |
| Thermal memory: | 20 minutes before and after tripping |
| Short-time pick-up adjustment type Isd: | Adjustable |
| [Isd] short-time pick-up adjustment range: | 1.5...10 x Ir |
| Short-time delay adjustment type: | Adjustable |
| [tsd] short-time delay adjustment range: | 0...0.4 s I²t=off0.1...0.4 s I²t=on |
| Instantaneous pick-up adjustment type Ii: | Adjustable |
| Instantaneous pick-up adjustment range: | 1.5...12 x In |
| Ground-fault pick-up adjustment type: | Adjustable |
| [Ig] ground-fault pick-up adjustment range: | 0.4...1 x In for In = 40 A0.2...1 x In for In > 40 AIg enable on/off |
| Ground-fault time delay adjustment type -tg: | Adjustable |
| [tg] ground-fault time delay adjustment range: | 0...0.4 s I²t=off0.1...0.4 s I²t=on |
| Earth-leakage protection: | Without |
| Zone selective interlocking ZSI: | With |
| Local signalling: | Flashing LED (green) for ready to operateLED 105 % Ir (red) for overloadLED 90 % Ir (orange) for overload |
| Display type: | LCD display |
| Type of measurement: | Energy meter |
| Communication of data: | Energy meteringProtection and alarm settingsTime-stamped histories and event tablesInstantaneous and demand valuesMaintenance indicatorsDemand current and powerPower qualityMaximeters/minimeters |
| Electrical data recording: | Maintenance indicators |
In short
Reference C4046E400
Product Name trip unit MicroLogic 6.3 E for ComPacT NSX 400/630 circuit breakers, electronic, rating 400A, 4 poles 4d - C4046E400
Range ComPacT nouvelle génération
Related Categories