Standards: | EN/IEC 61131-2EN/IEC 61010-2-201 |
---|
Product certifications: | C-TickcULus |
---|
Resistance to electrostatic discharge: | 8 kV in air conforming to EN/IEC 61000-4-24 kV on contact conforming to EN/IEC 61000-4-2 |
---|
Resistance to electromagnetic fields: | 10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-33 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-31 V/m 2 GHz...3 GHz conforming to EN/IEC 61000-4-3 |
---|
Resistance to magnetic fields: | 30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8 |
---|
Resistance to fast transients: | 1 kV for I/O conforming to EN/IEC 61000-4-4 |
---|
Surge withstand: | 1 kV I/O common mode conforming to EN/IEC 61000-4-5 DC |
---|
Resistance to conducted disturbances: | 10 V 0.15...80 MHz conforming to EN/IEC 61000-4-63 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL) |
---|
Electromagnetic emission: | Radiated emissions - test level: 40 dB?V/m QP class A ( 10 m) at 30...230 MHz conforming to EN/IEC 55011Radiated emissions - test level: 47 dB?V/m QP class A ( 10 m) at 230...1000 MHz conforming to EN/IEC 55011 |
---|
Ambient air temperature for operation: | -10...35 °C vertical installation-10...55 °C horizontal installation |
---|
Ambient air temperature for storage: | -25...70 °C |
---|
Relative humidity: | 10...95 %, without condensation (in operation)10...95 %, without condensation (in storage) |
---|
IP degree of protection: | IP20 with protective cover in place |
---|
Pollution degree: | 2 |
---|
Operating altitude: | 0...2000 m |
---|
Storage altitude: | 0...3000 m |
---|
Vibration resistance: | 3.5 mm at 5...8.4 Hz on DIN rail3 gn at 8.4...150 Hz on DIN rail3.5 mm at 5...8.4 Hz on panel3 gn at 8.4...150 Hz on panel |
---|
Shock resistance: | 15 gn for 11 ms |
---|
Sustainable offer status: | Green Premium productREACh Regulation |
---|