Technical informations
| Range: | TeSysTeSys Deca |
|---|---|
| Range of product: | TeSys D control relay |
| Product name: | TeSys CAD |
| Product or component type: | Control relay |
| Device short name: | CAD |
| Contactor application: | Control circuit |
| Utilisation category: | AC-14AC-15DC-13 |
|---|---|
| Pole contact composition: | 3 NO + 2 NC |
| [Ue] rated operational voltage: | |
| Control circuit type: | AC at 50/60 Hz |
| [Uc] control circuit voltage: | 440 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage: | 6Â kV conforming to IEC 60947 |
| [Ith] conventional free air thermal current: | 10 A (at 60 °C) |
| Irms rated making capacity: | 140Â A AC conforming to IEC 60947-5-1250Â A DC conforming to IEC 60947-5-1 |
| [Icw] rated short-time withstand current: | 100Â A - 1 s120Â A - 500 ms140Â A - 100 ms |
| Associated fuse rating: | 10Â A gG conforming to IEC 60947-5-1 |
| [Ui] rated insulation voltage: | 600Â V UL certified600Â V CSA certified690Â V conforming to IEC 60947-5-1 |
| Mounting support: | PlateRail |
| Connections - terminals: | Lugs-ring terminals (external diameter: 8Â mm) |
| Control circuit voltage limits: | 0.3...0.6 Uc (-40...70 °C):drop-out AC 50/60 Hz0.8...1.1 Uc (-40...60 °C):operational AC 50 Hz0.85...1.1 Uc (-40...60 °C):operational AC 60 Hz1...1.1 Uc (60...70 °C):operational AC 50/60 Hz |
| Operating time: | 12...22 ms coil energisation and NO closing4...12 ms coil de-energisation and NO opening4...19 ms coil energisation and NC opening6...17 ms coil de-energisation and NC closing |
| Mechanical durability: | 30Â Mcycles |
| Maximum operating rate: | 180Â cyc/mn |
| Inrush power in VA: | 70 VA 50 Hz (at 20 °C) |
| Hold-in power consumption in VA: | 8 VA 50 Hz (at 20 °C) |
| Minimum switching voltage: | 17Â V |
| Minimum switching current: | 5Â mA |
| Non-overlap time: | 1.5Â ms on energisation between NC and NO contact1.5Â ms on de-energisation between NC and NO contact |
| Insulation resistance: | > 10 MOhm |
| Mechanical robustness: | Shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27Shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27Vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6Vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 |
| Height: | 77Â mm |
| Width: | 45Â mm |
| Depth: | 84Â mm |
| Product weight: | 0.58Â kg |
| Compatibility code: | CAD |
In short
Reference CAD326R7
Product Name TeSys D control relay - 3 NO + 2 NC - <= 690 V - 440 V AC standard coil - CAD326R7
Range TeSys
Related Categories