calcActive())">
SCHNEIDER
Switch disconnector, ComPacT NSX160NA, 2 poles, fixed, thermal current Ith 160A - C162160S
C162160S
€218.45 Excl. Tax
€262.14 Inc. Tax
Excl. Tax
Excl. Tax
Incl. Tax
Incl. Tax
You save
Supply in process - Average delivery 4/6 weeks
- Technical support and dedicated single point of contact
- Free delivery from 250€ of purchase (Metropolitan France)
- 100% secure payments
Technical informations
| Range: | ComPacT new generation |
|---|---|
| Range of product: | ComPacT NSX100...250 new generation |
| Product name: | ComPacT NSX new generation |
| Device short name: | NSX160NA |
| Product or component type: | Switch disconnector |
| Device application: | Distribution |
| Poles description: | 2P |
| [Ith] conventional free air thermal current: | 160 A at 50 °C |
| [Ie] rated operational current: | AC-22A: 160 A AC 50/60 Hz 220...690 VAC-23A: 160 A AC 50/60 Hz 220...690 VDC-22A: 160 A DC 250 V 1 poleDC-22A: 160 A DC 500 V 2 poles in seriesDC-23A: 160 A DC 250 V 1 poleDC-23A: 160 A DC 500 V 2 poles in seriesDC-22A: 160 A DC 750 V 3 poles in seriesDC-23A: 160 A DC 750 V 3 poles in series |
| [In] rated current: | 160 A |
| [Ue] rated operational voltage: | 690 V AC 50/60 Hz750 V DC 3 poles in series500 V DC 2 poles in series250 V DC 1 pole |
| Network type: | ACDC |
| Network frequency: | 50/60 Hz |
| Suitability for isolation: | Yes conforming to EN/IEC 60947-3 |
| Utilisation category: | AC-22AAC-23ADC-22ADC-23A |
| Breaking capacity code: | NA |
| Contact position indicator: | Yes |
| Visible break: | No |
| Mounting mode: | Fixed |
| [Icw] rated short-time withstand current: | 2.5 kA during 1 s2.5 kA during 3 s0.96 kA during 20 s |
| [Icm] rated short-circuit making capacity: | 330 kA with upstream protection circuit breaker3.6 kA switch-disconnector alone |
| Control type: | Toggle |
| [Ui] rated insulation voltage: | 800 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage: | 8 kV |
| Mounting support: | Backplate |
|---|---|
| Upside connection: | Front |
| Downside connection: | Front |
| Connection pitch: | 35 mm |
| Mechanical durability: | 40000 cycles |
| Electrical durability: | AC-22A: 30000 cycles 440 V AC 50/60 Hz In/2AC-23A: 30000 cycles 440 V AC 50/60 Hz In/2AC-22A: 15000 cycles 440 V AC 50/60 Hz InAC-23A: 15000 cycles 440 V AC 50/60 Hz InAC-22A: 10000 cycles 690 V AC 50/60 Hz In/2AC-23A: 10000 cycles 690 V AC 50/60 Hz In/2AC-22A: 5000 cycles 690 V AC 50/60 Hz InAC-23A: 5000 cycles 690 V AC 50/60 Hz InDC-22A: 10000 cycles 250 V DC In/2 (1 pole)DC-23A: 10000 cycles 250 V DC In/2 (1 pole)DC-22A: 5000 cycles 500 V DC In (2 poles in series)DC-23A: 5000 cycles 500 V DC In (2 poles in series) |
| Width: | 105 mm |
| Height: | 161 mm |
| Depth: | 86 mm |
| Net weight: | 1.8 kg |
| Standards: | EN/IEC 60947-1EN/IEC 60947-3 |
| Product certifications: | CEEACCCC |
| Compatibility code: | NSX160 |
In short
Reference C162160S
Product Name Switch disconnector, ComPacT NSX160NA, 2 poles, fixed, thermal current Ith 160A - C162160S
Range ComPacT nouvelle génération
Related Categories