Poles description: | 3P |
---|
Network type: | AC |
---|
Utilisation category: | AC-3 conforming to IEC 60947-4-1Category A conforming to IEC 60947-2 |
---|
Network frequency: | 50/60 Hz conforming to IEC 60947-4-1 |
---|
Fixing mode: | 35 mm symmetrical DIN rail: clippedPanel: screwed (with 2 x M4 screws) |
---|
Operating position: | Any position |
---|
Motor power kW: | 7.5 kW at 400/415 V AC 50/60 Hz9 kW at 500 V AC 50/60 Hz15 kW at 690 V AC 50/60 Hz |
---|
Breaking capacity: | 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-210 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-24 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-220 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-250 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 |
---|
[Ics] rated service short-circuit breaking capacity: | 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-275 % at 500 V AC 50/60 Hz conforming to IEC 60947-250 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-275 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
---|
Control type: | Rotary knob |
---|
[In] rated current: | 18 A |
---|
Trip unit rating: | 13...18 A |
---|
Magnetic tripping current: | 223 A |
---|
[Ue] rated operational voltage: | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
---|
[Ui] rated insulation voltage: | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
---|
[Ith] conventional free air thermal current: | 18 A conforming to IEC 60947-4-1 |
---|
[Uimp] rated impulse withstand voltage: | 6 kV conforming to IEC 60947-2 |
---|
Power dissipation per pole: | 2.5 W |
---|
Mechanical durability: | 100000 cycles |
---|
Electrical durability: | 100000 cycles for AC-3 at 440 V |
---|
Maximum operating rate: | 25 cyc/h |
---|
Rated duty: | Continuous conforming to IEC 60947-4-1 |
---|
Direct connector: | Without |
---|
Tightening torque: | 1.7 N.m on screw clamp terminals |
---|
Suitability for isolation: | Yes conforming to IEC 60947-1 |
---|
Phase failure sensitivity: | Yes conforming to IEC 60947-4-1 |
---|
Height: | 89 mm |
---|
Width: | 45 mm |
---|
Depth: | 97 mm |
---|
Colour: | Dark grey |
---|
Compatibility code: | GV2P |
---|