Fixing mode: | 35 mm symmetrical DIN rail: clippedPanel: screwed (with 2 x M4 screws) |
---|
Operating position: | Any position |
---|
Motor power kW: | 1.1 kW at 400/415 V AC 50/60 Hz1.5 kW at 400/415 V AC 50/60 Hz1.5 kW at 500 V AC 50/60 Hz3 kW at 690 V AC 50/60 Hz |
---|
Control type: | Rotary knob |
---|
[In] rated current: | 4 A |
---|
[Ue] rated operational voltage: | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
---|
[Ui] rated insulation voltage: | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
---|
[Uimp] rated impulse withstand voltage: | 6 kV conforming to IEC 60947-2 |
---|
Power dissipation per pole: | 1.8 W |
---|
Mechanical durability: | 100000 cycles |
---|
Electrical durability: | 100000 cycles for AC-3 at 415 V |
---|
Maximum operating rate: | 40 cyc/h |
---|
Rated duty: | Continuous conforming to IEC 60947-4-1 |
---|
Direct connector: | Without |
---|
Connections - terminals: | Screw clamp terminals 2 cable(s) 1...6 mm² solidScrew clamp terminals 2 cable(s) 1.5...6 mm² flexible without cable endScrew clamp terminals 2 cable(s) 1...4 mm² flexible with cable end |
---|
Tightening torque: | 1.7 N.m on screw clamp terminals |
---|
Mechanical robustness: | Shocks: 30 Gn conforming to IEC 60068-2-27Vibrations: 5 Gn, 5...150 Hz conforming to IEC 60068-2-6 |
---|
Suitability for isolation: | Yes conforming to IEC 60947-1 |
---|
Height: | 89 mm |
---|
Width: | 45 mm |
---|
Depth: | 97 mm |
---|
Product weight: | 0.33 kg |
---|
Compatibility code: | GV2L |
---|