9,3/10 out of 1126 reviews
SCHNEIDER

TeSys D control relay - 5 NO - <= 690 V - 24 V DC standard coil - CAD503BD

CAD503BD

€57.69 Excl. Tax
€69.23 Inc. Tax
Supply in process – Average delivery time 4/6 weeks
  • Technical support and dedicated single point of contact
  • Free delivery from 100€ of purchase (Metropolitan France)
  • 100% secure payments
Technical informations
Range: TeSysTeSys Deca
Range of product: TeSys D control relay
Product name: TeSys CAD
Product or component type: Control relay
Device short name: CAD
Contactor application: Control circuit
Utilisation category: DC-13AC-15AC-14
Pole contact composition: 5 NO
[Ue] rated operational voltage:
Control circuit type: DC standard
[Uc] control circuit voltage: 24 V DC
[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947
[Ith] conventional free air thermal current: 10 A (at 60 °C)
Irms rated making capacity: 140 A AC conforming to IEC 60947-5-1250 A DC conforming to IEC 60947-5-1
[Icw] rated short-time withstand current: 100 A - 1 s120 A - 500 ms140 A - 100 ms
Associated fuse rating: 10 A gG conforming to IEC 60947-5-1
[Ui] rated insulation voltage: 600 V UL certified600 V CSA certified690 V conforming to IEC 60947-5-1
Mounting support: RailPlate
Connections - terminals: Spring terminals 1 cable(s) 1...2.5 mm²flexible without cable endSpring terminals 2 cable(s) 1...2.5 mm²flexible without cable endSpring terminals 1 cable(s) 1...2.5 mm²solid without cable endSpring terminals 2 cable(s) 1...2.5 mm²solid without cable end
Control circuit voltage limits: 0.1...0.25 Uc (-40...70 °C):drop-out DC0.7...1.25 Uc (-40...60 °C):operational DC1...1.25 Uc (60...70 °C):operational DC
Operating time: 53...72 ms coil energisation and NO closing16...24 ms coil de-energisation and NO opening
Mechanical durability: 30 Mcycles
Maximum operating rate: 180 cyc/mn
Time constant: 28 ms
Inrush power in W: 5.4 W (at 20 °C)
Hold-in power consumption in W: 5.4 W at 20 °C
Minimum switching voltage: 17 V
Minimum switching current: 5 mA
Non-overlap time: 1.5 ms on energisation between NC and NO contact1.5 ms on de-energisation between NC and NO contact
Insulation resistance: > 10 MOhm
Mechanical robustness: Shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27Shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27Vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6Vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
Height: 99 mm
Width: 45 mm
Depth: 93 mm
Product weight: 0.58 kg
Compatibility code: CAD
In short
Reference CAD503BD
Product Name TeSys D control relay - 5 NO - <= 690 V - 24 V DC standard coil - CAD503BD
Range TeSys
Related Categories