9,3/10 out of 1126 reviews
SCHNEIDER

limit switch XCKM - thermoplastic roller lever plunger - 1NC+1NO - snap - M20 - XCKM121H29

XCKM121H29

€38.64 Excl. Tax
€46.37 Inc. Tax
available In stock more than 100 units – Dispatched within 24/48h
  • check2 Technical support and dedicated single point of contact
  • check2 Free delivery from 100€ of purchase (Metropolitan France)
  • check2 100% secure payments maestro mastercard paypal visa payplug fintecture alma
Technical informations
Range of product: Telemecanique Limit switches XC Standard
Series name: Standard format
Product or component type: Limit switch
Device short name: XCKM
Body type: Fixed
Head type: Plunger head
Material: Metal
Body material: Zamak
Fixing mode: By the body
Movement of operating head: Linear
Type of operator: Spring return roller lever plunger thermoplastic
Type of approach: Lateral approach, 1 direction
Cable entry: 3 entries tapped for M20 x 1.5 cable gland, cable outer diameter: 7...13 mm
Number of poles: 2
Contacts type and composition: 1 NC + 1 NO
Contact operation: Snap action
Switch actuation: By 30° cam
Electrical connection: Screw-clamp terminals, clamping capacity: 1 x 0.34...2 x 1.5 mm²
Contacts insulation form: Zb
Number of steps: 1
Positive opening: With
Positive opening minimum force: 24 N
Minimum force for tripping: 8 N
Minimum actuation speed: 0.01 m/min
Maximum actuation speed: 1.5 m/s
Contact code designation: A300, AC-15 (Ue = 240 V), Ie = 3 A conforming to EN/IEC 60947-5-1 appendix AQ300, DC-13 (Ue = 250 V), Ie = 0.27 A conforming to EN/IEC 60947-5-1 appendix A
[Ithe] conventional enclosed thermal current: 10 A AC
[Ui] rated insulation voltage: 300 V conforming to UL 508500 V (pollution degree 3) conforming to IEC 60947-1300 V conforming to CSA C22.2 No 14
Maximum resistance across terminals: 25 MOhm conforming to IEC 60255-7 category 3
[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 606646 kV conforming to IEC 60947-1
Short-circuit protection: 10 A cartridge fuse, type gG
Electrical durability: 5000000 cycles, DC-13, inductive load type, 120 V, 4 W, operating rate 5000000 cycles, DC-13, inductive load type, 24 V, 7 W, operating rate 5000000 cycles, DC-13, inductive load type, 48 V, 10 W, operating rate
Mechanical durability: 20000000 cycles
Width: 64 mm
Height: 64 mm
Depth: 30 mm
Product weight: 0.3 kg
Terminals description ISO n°1: (13-14)NO(21-22)NC
Device presentation: Complete product
Compatibility code: XCKM
Specific application: Classic
In short
Reference XCKM121H29
Product Name limit switch XCKM - thermoplastic roller lever plunger - 1NC+1NO - snap - M20 - XCKM121H29
Related Categories