SCHNEIDER
RELAIS UNIVERSEL 2 CO (CYLIND) 24 V DC - RUMC2AB1BD
RUMC2AB1BD
Obsolete product, here is the proposed substitution for the reference RUMC2AB1BD : RUMC21BD
Technical informations
Range of product: | Zelio Relay |
---|---|
Series name: | Universal |
Product or component type: | Plug-in relay |
Device short name: | RUM |
Contacts type and composition: | 2 C/O |
[Uc] control circuit voltage: | 24 V DC |
[Ithe] conventional enclosed thermal current: | 10 A at -40...55 °C |
Status LED: | Without |
Control type: | Lockable test button |
Utilisation coefficient: | 20 % |
Shape of pin: | Cylindrical |
---|---|
[Ui] rated insulation voltage: | 250 V conforming to IEC300 V conforming to UL300 V conforming to CSA |
[Uimp] rated impulse withstand voltage: | 4 kV |
Contacts material: | AgNi |
[Ie] rated operational current: | 10 A AC-1/DC-1 (NO) conforming to IEC5 A AC-1/DC-1 (NC) conforming to IEC12 A at 28 V DC-1 conforming to UL16 A at 277 V AC-1 conforming to UL |
Minimum switching current: | 10 mA |
Maximum switching voltage: | 250 V AC conforming to IEC250 V DC conforming to IEC |
Minimum switching voltage: | 17 V |
Load current: | 10 A at 250 V AC10 A at 28 V DC |
Maximum switching capacity: | 2500 VA, AC circuit280 W, DC circuit |
Minimum switching capacity: | 170 mW |
Operating rate: | |
Mechanical durability: | 5000000 cycles |
Electrical durability: | 100000 cycles for resistive load |
Average coil consumption: | 1.4 W |
Drop-out voltage threshold: | >= 0.1 Uc DC |
Operating time: | 20 ms |
Average resistance: | 470 Ohm at 20 °C +/- 10 % |
Rated operational voltage limits: | 19.2...26.4 V DC |
Protection category: | RT I |
Safety reliability data: | B10d = 100000 |
Operating position: | Any position |
Product weight: | 0.085 kg |
In short
Reference RUMC2AB1BD
Product Name RELAIS UNIVERSEL 2 CO (CYLIND) 24 V DC - RUMC2AB1BD
Related Categories