[Ie] rated operational current: | 80 A at 500 V AC 50/60 Hz |
---|
[Ue] rated operational voltage: | 500 V AC 50/60 Hz |
---|
[Icm] rated short-circuit making capacity: | 2 kA switch-disconnector alone |
---|
[Icw] rated short-time withstand current: | 1.5 kA during 50 ms conforming to IEC 60947-3 |
---|
[Ui] rated insulation voltage: | 690 V AC 50/60 Hz conforming to IEC 60947-3 |
---|
[Uimp] rated impulse withstand voltage: | 8 kV conforming to IEC 60947-3 |
---|
Contact position indicator: | Yes |
---|
Control type: | ToggleManual tripping test |
---|
Local signalling: | Trip indicatorON/OFF indication |
---|
Mounting mode: | Fixed |
---|
Mounting support: | 35 mm symmetrical DIN rail |
---|
9 mm pitches: | 12 |
---|
Height: | 103 mm |
---|
Width: | 108 mm |
---|
Depth: | 81 mm |
---|
Product weight: | 0.96 kg |
---|
Colour: | Black |
---|
Mechanical durability: | 20000 cycles |
---|
Electrical durability: | Category A (except AC20, DC20): 1500 cycles AC 50/60 Hz conforming to IEC 60947-3Category B (except AC20, DC20): 300 cycles AC 50/60 Hz conforming to IEC 60947-3 |
---|
Provision for padlocking: | Padlockable |
---|
Locking options description: | Integrated padlocking |
---|
Connections - terminals: | Tunnel type terminals (top or bottom) 16...70 mm² rigidTunnel type terminals (top or bottom) 10...50 mm² flexible |
---|
Wire stripping length: | Power circuit: 20 mm for top or bottom connection |
---|
Tightening torque: | Power circuit: 6 N.m top or bottom |
---|
Compatibility code: | NG125 |
---|