Technical informations
| Range of product: | Preventa Safety automation |
|---|---|
| Product or component type: | Preventa safety module |
| Safety module name: | XPSAC |
| Safety module application: | For emergency stop and switch monitoring |
| Function of module: | Emergency stopSwitch monitoring |
| Safety level: | Can reach PL e/category 4 conforming to EN/ISO 13849-1Can reach SILCL 3 conforming to EN/IEC 62061 |
| Safety reliability data: | MTTFd = 210.4 years conforming to EN/ISO 13849-1DC > 99 % conforming to EN/ISO 13849-1PFHd = 3.56E-9 1/h conforming to EN/IEC 62061 |
| Type of start: | Unmonitored |
| Connections - terminals: | Captive screw clamp terminals, 1 x 0.14...1 x 2.5 mm² flexible without cable endCaptive screw clamp terminals, 1 x 0.14...1 x 2.5 mm² solid without cable endCaptive screw clamp terminals, 1 x 0.25...1 x 1.5 mm² flexible with cable end, with bezelCaptive screw clamp terminals, 1 x 0.25...1 x 2.5 mm² flexible with cable end, without bezelCaptive screw clamp terminals, 2 x 0.14...2 x 0.75 mm² flexible without cable endCaptive screw clamp terminals, 2 x 0.14...2 x 0.75 mm² solid without cable endCaptive screw clamp terminals, 2 x 0.25...2 x 1 mm² flexible with cable end, without bezelCaptive screw clamp terminals, 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel |
| Output type: | Relay instantaneous opening, 3 NO circuit(s), volt-free |
| Number of additional circuits: | 1 solid state output |
| [Us] rated supply voltage: | 24 V AC - 20...10 %24 V DC - 20...20 % |
| Supply frequency: | 50/60 Hz |
|---|---|
| Maximum power consumption in W: | 1.2 W DC |
| Maximum power consumption in VA: | 2.5 VA AC |
| [Uc] control circuit voltage: | 24 V |
| Breaking capacity: | 180 VA holding AC-15 C300 relay output1800 VA inrush AC-15 C300 relay output |
| Breaking capacity: | 1.5 A at 24 V (DC-13) time constant: 50 ms for relay output |
| Output thermal current: | 6 A per relay for relay output |
| [Ith] conventional free air thermal current: | 10.5 A |
| Associated fuse rating: | 4 A gG or gL for relay output conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 2006 A fast blow for relay output conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200 |
| Minimum output current: | 10 mA for relay output |
| Minimum output voltage: | 16 V for relay output |
| Maximum response time on input open: | 100 ms |
| [Ui] rated insulation voltage: | 300 V (pollution degree 2) conforming to IEC 60947-5-1300 V (pollution degree 2) conforming to DIN VDE 0110 part 1 |
| [Uimp] rated impulse withstand voltage: | 4 kV overvoltage category III conforming to IEC 60947-5-14 kV overvoltage category III conforming to DIN VDE 0110 part 1 |
| Local signalling: | 2 LEDs |
| Current consumption: | 40 mA at 24 V DC on power supply90 mA at 24 V AC on power supply |
| Mounting support: | 35 mm symmetrical DIN rail |
| Product weight: | 0.16 kg |