calcActive())">
SCHNEIDER
Modular 1-phase current control relay, 5 A, 2 CO, 0.15…15 A,, 24…240 V AC/DC - RM35JA32MR
RM35JA32MR
€144.16 Excl. Tax
€172.99 Inc. Tax
Excl. Tax
Excl. Tax
Incl. Tax
Incl. Tax
You save
In stock – Dispatched within 24/48h
- Technical support and dedicated single point of contact
- Free delivery from 250€ of purchase (Metropolitan France)
- 100% secure payments
Technical informations
| Range of product: | Harmony Control Relays |
|---|---|
| Product or component type: | Current control relay |
| Relay type: | Current control relay |
| Relay name: | RM35JA |
| Relay monitored parameters: | Overcurrent or undercurrent in window modeOvercurrent or undercurrent detection |
| Time delay type: | Adjustable 0.1...30 s, +/- 10 % of the full scale value on crossing the threshold Tt |
| Switching capacity in VA: | 2000 VA |
| Measurement range: | 0.15...1.5 A E1-M terminals0.5...5 A E2-M terminals1.5...15 A E3-M terminals150 mA...15 A current AC/DC 50/60 Hz |
| Contacts type and composition: | 2 C/O |
| Connections - terminals: | Screw connectors |
| [Uc] control circuit voltage: | 24...240 V |
| [In] rated current: | 8 A |
| Reset time: | 1500 ms at maximum voltage |
|---|---|
| Maximum switching voltage: | 250 V AC |
| Minimum switching current: | 10 mA at 5 V DC |
| Maximum switching current: | 8 A AC |
| [Us] rated supply voltage: | 24...240 V AC/DC 50/60 Hz +/- 10 % |
| Supply voltage limits: | 20.4...264 V AC/DC |
| Control circuit voltage limits: | - 15 % + 10 % Un |
| Power consumption in VA: | 3.5 VA AC |
| Maximum power consumption in W: | 1.5 W DC |
| Resistance across terminals: | 0.005 Ohm at E3-M terminals0.015 Ohm at E2-M terminals0.05 Ohm at E1-M terminals |
| Output contacts: | 2 C/O |
| Nominal output current: | 8 A |
| Internal input resistance: | 0.015 Ohm0.005 Ohm0.05 Ohm |
| Setting accuracy of the switching threshold: | +/- 10 % of the full scale |
| Switching threshold drift: | |
| Setting accuracy of time delay: | 10 P |
| Time delay drift: | |
| Hysteresis: | 5...50 % adjustable of threshold setting for overcurrent or undercurrent detection3 % fixed of full scale for window mode |
| Run-up delay at power-up: | 0.3 s |
| Maximum measuring cycle: | 100 ms measurement cycle as true rms value |
| Repeat accuracy: | +/- 0.5 % for input and measurement circuit+/- 2 % for time delay |
| Measurement error: | 0.05 %/°C with temperature variation |
| Response time: | |
| Threshold setting: | 10...100 % |
| Overvoltage category: | III conforming to IEC 60664-1III conforming to UL 508 |
| Insulation resistance: | > 100 MOhm at 500 V DC conforming to IEC 60255-27 |
| Insulation: | Between supply and measurement |
| Mounting position: | Any position |
| Connections - terminals: | Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable endScrew terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable endScrew terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable endScrew terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end |
| Tightening torque: | 0.6...1 N.m conforming to IEC 60947-1 |
| Housing material: | Self-extinguishing plastic |
| Status LED: | LED (yellow)relay ONLED (green)power ON |
| Mounting support: | 35 mm DIN rail conforming to EN/IEC 60715 |
| Electrical durability: | 100000 cycles |
| Mechanical durability: | 10000000 cycles |
| Utilisation category: | AC-15 conforming to IEC 60947-5-1DC-13 conforming to IEC 60947-5-1AC-1 conforming to IEC 60947-4-1DC-1 conforming to IEC 60947-4-1 |
| Safety reliability data: | MTTFd = 296.8 yearsB10d = 270000 |
| Contacts material: | Cadmium free |
| Width: | 35 mm |
| Product weight: | 0.12 kg |
| Functionality: | Overcurrent or undercurrent detection |
| Compatibility code: | RM3 |
In short
Reference RM35JA32MR
Product Name Modular 1-phase current control relay, 5 A, 2 CO, 0.15…15 A,, 24…240 V AC/DC - RM35JA32MR
Related Categories