calcActive())">
SCHNEIDER
Miniature circuit-breaker, Acti9 iDT40T, 1P+N, 10 A, B curve, 4500 A (IEC 60898-1), 6 kA (IEC 60947-2) - A9P12610
A9P12610
€22.93 Excl. Tax
€27.52 Inc. Tax
Excl. Tax
Excl. Tax
Incl. Tax
Incl. Tax
You save
In stock more than 100 units – Dispatched within 24/48h
- Technical support and dedicated single point of contact
- Free delivery from 250€ of purchase (Metropolitan France)
- 100% secure payments
Technical informations
| Range: | Acti9 |
|---|---|
| Product name: | Acti9 iDT40 |
| Product or component type: | Miniature circuit-breaker |
| Device short name: | IDT40T |
| Device application: | Distribution |
| Poles description: | 1P + N |
| Number of protected poles: | 1 |
| Neutral position: | Left |
| [In] rated current: | 10 A |
| Network type: | AC |
| Trip unit technology: | Thermal-magnetic |
| Curve code: | B |
| Breaking capacity code: | T |
| Breaking capacity: | 4500 A Icn at 230 V AC 50 Hz conforming to EN/IEC 60898-16 kA Icu at 230 V AC 50 Hz conforming to EN/IEC 60947-2 |
| Suitability for isolation: | Yes conforming to EN/IEC 60947-2 |
| Quality labels: | NF |
| Network frequency: | 50 Hz |
|---|---|
| [Ue] rated operational voltage: | 230 V AC 50 Hz |
| Magnetic tripping limit: | 3...5 x In conforming to EN/IEC 60898-14 x In +/- 20 % conforming to EN/IEC 60947-2 |
| [Ics] rated service breaking capacity: | 4500 A 100 % x Icn at 230 V AC 50 Hz conforming to EN/IEC 60898-14.5 kA 75 % x Icu at 230 V AC 50 Hz conforming to EN/IEC 60947-2 |
| Limitation class: | 3 conforming to EN/IEC 60898-1 |
| [Ui] rated insulation voltage: | 400 V AC 50 Hz conforming to EN/IEC 60947-2 |
| [Uimp] rated impulse withstand voltage: | 4 kV conforming to EN/IEC 60947-2 |
| Contact position indicator: | Yes |
| Control type: | Toggle |
| Local signalling: | ON/OFF indicationTrip indicator |
| Mounting mode: | Clip-on |
| Mounting support: | DIN rail |
| 9 mm pitches: | 2 |
| Height: | 85 mm |
| Width: | 18 mm |
| Depth: | 74 mm |
| Product weight: | 120 g |
| Colour: | White |
| Mechanical durability: | 20000 cycles |
| Electrical durability: | 20000 cycles |
| Locking options description: | Padlocking device |
| Top connection: | Screw |
| Bottom connection: | Screw |
| Connections - terminals: | Tunnel type terminals top or bottom 1...10 mm² flexibleTunnel type terminals top or bottom 1...16 mm² rigid |
| Wire stripping length: | 14 mm for top or bottom connection |
| Tightening torque: | 2 N.m top or bottom |
| Earth-leakage protection: | Separate block |
| Compatibility code: | IDT40T |
In short
Reference A9P12610
Product Name Miniature circuit-breaker, Acti9 iDT40T, 1P+N, 10 A, B curve, 4500 A (IEC 60898-1), 6 kA (IEC 60947-2) - A9P12610
Range Acti9
Device function Distribution
Related Categories