Network frequency: | 0...400 Hz |
---|
Mounting support: | Plate, with specific accessoriesRail, with specific accessoriesUnder contactor |
---|
Tripping threshold: | 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1 |
---|
Auxiliary contact composition: | 1 NO + 1 NC |
---|
[Ith] conventional free air thermal current: | 5 A for signalling circuit |
---|
Permissible current: | 1.5 A at 240 V AC-15 for signalling circuit0.1 A at 250 V DC-13 for signalling circuit |
---|
[Ue] rated operational voltage: | 690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1 |
---|
Associated fuse rating: | 4 A gG for signalling circuit4 A BS for signalling circuit |
---|
[Uimp] rated impulse withstand voltage: | 6 kV |
---|
Phase failure sensitivity: | Tripping current 130 % of Ir on two phase, the last one at 0 |
---|
Control type: | Red push-button: stopBlue push-button: reset |
---|
Temperature compensation: | -20...60 °C |
---|
Connections - terminals: | Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm² flexible without cable endControl circuit: screw clamp terminals 2 cable(s) 1...2.5 mm² flexible with cable endControl circuit: screw clamp terminals 2 cable(s) 1...2.5 mm² solidPower circuit: screw clamp terminals 1 cable(s) 1.5...10 mm² flexible without cable endPower circuit: screw clamp terminals 1 cable(s) 1...6 mm² flexible with cable endPower circuit: screw clamp terminals 1 cable(s) 1.5...10 mm² solid |
---|
Tightening torque: | Control circuit: 1.7 N.m - on screw clamp terminalsPower circuit: 2.5 N.m - on screw clamp terminals |
---|
Height: | 66 mm |
---|
Width: | 45 mm |
---|
Depth: | 70 mm |
---|
Product weight: | 0.124 kg |
---|
Compatibility code: | LRD |
---|