9,3/10 out of 1126 reviews
SCHNEIDER

TeSys F contactor - 3P(3 NO)-AC-3 <= 440V 150A with coil LX9 - 24...600V AC 40/400Hz, LX4 - 24...460V DC, LXE - 100...250V AC 50/60Hz or 100…380V DC - LC1F150

LC1F150

obsolete product
Technical informations
Range of product: TeSys F
Range: TeSys
Product name: TeSys F
Product or component type: Contactor
Device short name: LC1F
Contactor application: Resistive loadMotor control
Utilisation category: AC-1AC-4AC-3
Poles description: 3P
Pole contact composition: 3 NO
[Ue] rated operational voltage:
[Ie] rated operational current: 250 A (at 150 A (at
Motor power kW: 75 kW at 380...400 V AC 50/60 Hz (AC-3)80 kW at 415 V AC 50/60 Hz (AC-3)80 kW at 440 V AC 50/60 Hz (AC-3)90 kW at 500 V AC 50/60 Hz (AC-3)40 kW at 220...240 V AC 50/60 Hz (AC-3)100 kW at 660...690 V AC 50/60 Hz (AC-3)22 kW at 400 V AC 50/60 Hz (AC-4)
[Uc] control circuit voltage: 24...575 V AC 40...400 Hz with LX1/LX9 coil24...460 V DC with LX4 coil100...250 V AC 50/60 Hz with LXE coil100...380 V DC with LXE coil
[Uimp] rated impulse withstand voltage: 8 kV
Overvoltage category: III
[Ith] conventional free air thermal current: 250 A (at 40 °C)
Irms rated making capacity: 1500 A conforming to IEC 60947-4-1
Rated breaking capacity: 1200 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current: 1200 A 40 °C - 10 s700 A 40 °C - 30 s600 A 40 °C - 1 min450 A 40 °C - 3 min350 A 40 °C - 10 min
Associated fuse rating: 160 A aM at 250 A gG at
Average impedance: 0.35 mOhm - Ith 250 A 50 Hz
[Ui] rated insulation voltage: 1000 V conforming to IEC 60947-4-11500 V conforming to VDE 0110 group C
Control circuit voltage limits: Operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coilDrop-out: 0.2...0.55 Uc AC 40...400 Hz with LX1/LX9 coilOperational: 0.85...1.1 Uc DC with LX4 coilDrop-out: 0.15...0.2 Uc DC with LX4 coilOperational: 85...275 V AC 50/60 Hz with LXE coilDrop-out: 0...60 V AC 50/60 Hz with LXE coilOperational: 85...418 V DC with LXE coilDrop-out: 0...45 V DC with LXE coil
Power dissipation per pole: 22 W AC-18 W AC-3
Heat dissipation: 5.9...7.2 W2.2...2.5 W
Operating time: 35 ms closing for with LX1/LX9 coil130 ms opening for with LX1/LX9 coil30...40 ms closing for with LX4 coil30...50 ms opening for with LX4 coil40...80 ms closing for with LXE coil6...54 ms opening for with LXE coil
Mounting support: Plate
Standards: IEC 60947-4-1EN 60947-4-1IEC 60947-1EN 60947-1JIS C8201-4-1
Product certifications: RINACSABVRMRoSLROS (Lloyds register of shipping)DNVABSULCBUKCA
Connections - terminals: Power circuit: lugs-ring terminals 1 cable(s) 120 mm² - busbar cross section: 25 x 3 mmPower circuit: connector 1 cable(s) 120 mm²Power circuit: bar 2 cable(s) Power circuit: bolted connectionControl circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable endControl circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible with cable endControl circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable endControl circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²solid without cable endControl circuit: screw clamp terminals 1 cable(s) 1...4 mm²Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²Control circuit: screw clamp terminals 1.0 cable(s) 0.2...2.5 mm²flexible without cable endControl circuit: screw clamp terminals 1.0 cable(s) 0.25...2.5 mm²flexible with cable endControl circuit: screw clamp terminals 1.0 cable(s) 0.2...2.5 mm²solid without cable end
Tightening torque: Power circuit: 18 N.mControl circuit: 1.2 N.mControl circuit: 0.6 N.m
Mechanical durability: 10 Mcycles
Inrush power in VA: 690...855 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil543...665 VA (at 20 °C)with LX4 coil280...310 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil270...320 VA (at 20 °C)with LXE coil
Hold-in power consumption in VA: 6.6...8.1 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil3.94...4.83 VA (at 20 °C)with LX4 coil4.5...7.0 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil2.5...4.0 VA (at 20 °C)with LXE coil
Maximum operating rate: 2400 cyc/h 55 °C
Compatibility code: LC1F
In short
Reference LC1F150
Product Name TeSys F contactor - 3P(3 NO)-AC-3 <= 440V 150A with coil LX9 - 24...600V AC 40/400Hz, LX4 - 24...460V DC, LXE - 100...250V AC 50/60Hz or 100…380V DC - LC1F150
Range TeSys
Related Categories