9,3/10 out of 1126 reviews
SCHNEIDER

contacteur TeSys LC1D 3P AC3 440V 40 A bobine 230 V CA  - LC1D40P7

LC1D40P7

Obsolete product, here is the proposed substitution for the reference LC1D40P7 : LC1D40AP7
Technical informations
Range of product: TeSys D
Range: TeSys
Product or component type: Contactor
Device short name: LC1D
Contactor application: Motor controlResistive load
Utilisation category: AC-1AC-4AC-3AC-2
Control circuit type: AC 50/60 Hz
Poles description: 3P
Pole contact composition: 3 NO
[Ie] rated operational current: 40 A (60 A (
Motor power kW: 18.5 kW at 380...400 V AC 50/60 Hz AC-322 kW at 1000 V AC 50/60 Hz AC-322 kW at 415 V AC 50/60 Hz AC-322 kW at 440 V AC 50/60 Hz AC-322 kW at 500 V AC 50/60 Hz AC-330 kW at 660...690 V AC 50/60 Hz AC-311 kW at 220...230 V AC 50/60 Hz AC-39 kW at 400 V AC 50/60 Hz AC-4
Motor power hp: 10 hp at 200/208 V AC 60 Hz for 3P motors conforming to CSA10 hp at 200/208 V AC 60 Hz for 3P motors conforming to UL10 hp at 230/240 V AC 60 Hz for 3P motors conforming to CSA10 hp at 230/240 V AC 60 Hz for 3P motors conforming to UL3 hp at 115 V AC 60 Hz for 1P motors conforming to CSA3 hp at 115 V AC 60 Hz for 1P motors conforming to UL30 hp at 460/480 V AC 60 Hz for 3P motors conforming to CSA30 hp at 460/480 V AC 60 Hz for 3P motors conforming to UL30 hp at 575/600 V AC 60 Hz for 3P motors conforming to CSA30 hp at 575/600 V AC 60 Hz for 3P motors conforming to UL5 hp at 230/240 V AC 60 Hz for 1P motors conforming to CSA5 hp at 230/240 V AC 60 Hz for 1P motors conforming to UL
[Uc] control circuit voltage: 230 V AC 50/60 Hz
Connections - terminals: Control circuit
Coil technology: Without built-in bidirectional peak limiting diode suppressor
Protective cover: With
Auxiliary contacts type: Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1Type mirror contact (1 NC) conforming to IEC 60947-4-1
Auxiliary contact composition: 1 NO + 1 NC
Control circuit voltage limits: 0.3...0.6 Uc at 60 °C drop-out 50/60 Hz0.8...1.1 Uc at 60 °C operational 50 Hz0.85...1.1 Uc at 60 °C operational 60 Hz
[Ui] rated insulation voltage: 600 V for control circuit certifications CSA600 V for control circuit certifications UL600 V for power circuit certifications CSA600 V for power circuit certifications UL690 V for control circuit conforming to IEC 60947-1690 V for power circuit conforming to IEC 60947-1
[Uimp] rated impulse withstand voltage: 8 kV IEC 60947
Overvoltage category: III
Mounting support: PlateRail
Flame retardance: V1 conforming to UL 94
Tightening torque: Power circuit
[Ue] rated operational voltage:
[Ith] conventional free air thermal current: 10 A at 60 A at
Irms rated making capacity: 140 A AC for control circuit conforming to IEC 60947-5-1800 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity: 800 A at 440 V for power circuit conforming to IEC 60947
Associated fuse rating: 10 A gG for control circuit conforming to IEC 60947-5-180 A gG at 80 A gG at
Power dissipation per pole: 5.4 W AC-12.4 W AC-3
Inrush power in VA: 140 VA at 20 °C (cos f 0.75)160 VA at 20 °C (cos f 0.75)
Hold-in power consumption in VA: 13 VA at 20 °C (cos f 0.3) 60 Hz15 VA at 20 °C (cos f 0.3) 50 Hz
Operating time: 12...26 ms closing4...19 ms opening
Safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability: 6000000 cycles
Operating rate: 3600 cyc/h at
Minimum switching current: 5 mA for control circuit
Minimum switching voltage: 17 V for control circuit
Non-overlap time: 1.5 ms on de-energisation between NC and NO contacts1.5 ms on energisation between NC and NO contacts
Insulation resistance: > 10 MOhm for control circuit
Height: 127 mm
Width: 75 mm
Depth: 119 mm
Product weight: 1.4 kg
In short
Reference LC1D40P7
Product Name contacteur TeSys LC1D 3P AC3 440V 40 A bobine 230 V CA  - LC1D40P7
Range TeSys
Related Categories