9,3/10 out of 1126 reviews
SCHNEIDER

TeSys LC1D - contacteur - 3P - AC-3 440V - 115A - bobine 110Vca  - LC1D1156F5

LC1D1156F5

€462.09 Excl. Tax
€554.51 Inc. Tax
preorder Supply in process – Average delivery time 4/6 weeks
  • check2 Technical support and dedicated single point of contact
  • check2 Free delivery from 100€ of purchase (Metropolitan France)
  • check2 100% secure payments maestro mastercard paypal visa payplug fintecture alma
Technical informations
Range of product: TeSys D
Range: TeSys
Product name: TeSys D
Product or component type: Contactor
Device short name: LC1D
Contactor application: Resistive loadMotor control
Utilisation category: AC-3AC-1AC-4
Poles description: 3P
Pole contact composition: 3 NO
[Ue] rated operational voltage:
[Ie] rated operational current: 200 A (115 A (
Motor power kW: 55 kW at 380...400 V AC 50/60 Hz AC-375 kW at 500 V AC 50/60 Hz AC-380 kW at 660...690 V AC 50/60 Hz AC-330 kW at 220...230 V AC 50/60 Hz AC-359 kW at 415...440 V AC 50/60 Hz AC-365 kW at 1000 V AC 50/60 Hz AC-318.5 kW at 400 V AC 50/60 Hz AC-4
Motor power hp: 30 hp at 200/208 V AC 50/60 Hz for 3 phases motors40 hp at 230/240 V AC 50/60 Hz for 3 phases motors75 hp at 460/480 V AC 50/60 Hz for 3 phases motors100 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Control circuit type: AC 50 Hz
Control circuit voltage: 110 V AC 50 Hz
Auxiliary contact composition: 1 NO + 1 NC
[Uimp] rated impulse withstand voltage: Conforming to IEC 60947
Overvoltage category: III
[Ith] conventional free air thermal current: 200 A at
Irms rated making capacity: 1260 A at 440 V for power circuit conforming to IEC 60947140 A AC for signalling circuit conforming to IEC 60947-5-1250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity: 1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current: 1100 A 100 A 1 s signalling circuit120 A 500 ms signalling circuit140 A 100 ms signalling circuit250 A 550 A 950 A
Associated fuse rating: 200 A gG at 250 A gG at 10 A gG for signalling circuit
Average impedance: 0.6 mOhm at 50 Hz - Ith 200 A for power circuit
[Ui] rated insulation voltage: 1000 V for power circuit conforming to IEC 60947-4-1600 V for power circuit certifications CSA600 V for power circuit certifications UL690 V for signalling circuit conforming to IEC 60947-1600 V for signalling circuit certifications CSA600 V for signalling circuit certifications UL
Electrical durability: 0.8 Mcycles 200 A AC-1 at Ue 0.95 Mcycles 115 A AC-3 at Ue
Power dissipation per pole: 24 W AC-17.9 W AC-3
Protective cover: With
Mounting support: RailPlate
Standards: CSA C22.2 No 14EN 60947-4-1EN 60947-5-1IEC 60947-4-1IEC 60947-5-1UL 508
Product certifications: CSADNVCCCRINAGLLROSGOSTBVUL
Connections - terminals: Power circuit
Tightening torque: Control circuit
Operating time: 6...20 ms opening20...50 ms closing
Safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability: 8 Mcycles
Operating rate: 2400 cyc/h at
Coil technology: Without built-in suppressor module
Control circuit voltage limits: 0.3...0.6 Uc drop-out at 55 °C, AC 50 Hz0.85...1.1 Uc operational at 55 °C, AC 50 Hz
Inrush power in VA: 300 VA at 20 °C (cos ? 0.8) 50 Hz
Hold-in power consumption in VA: 22 VA at 20 °C (cos ? 0.3) 50 Hz
Heat dissipation: 3...8 W at 50 Hz
Auxiliary contacts type: Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1Type mirror contact (1 NC) conforming to IEC 60947-4-1
Signalling circuit frequency: 25...400 Hz
Minimum switching current: 5 mA for signalling circuit
Minimum switching voltage: 17 V for signalling circuit
Non-overlap time: 1.5 ms on de-energisation (between NC and NO contact)1.5 ms on energisation (between NC and NO contact)
Insulation resistance: > 10 MOhm for signalling circuit
In short
Reference LC1D1156F5
Product Name TeSys LC1D - contacteur - 3P - AC-3 440V - 115A - bobine 110Vca  - LC1D1156F5
Range TeSys