Network rated voltage: | 0...480 V - AC at 45...440 Hz (device connected to phase) 0...830 V - AC at 45...440 Hz (device connected to neutral) 0...480 V - DC |
---|
Insulation shield: | No |
---|
Type of measurement: | Network insulation resistance - measurement range: 10 Ohm...10 MOhmEarth leakage capacitance - measurement range: 0.1...500 µF |
---|
Local signalling: | Green indicator light: satisfactory insulation resistanceWhite indicator light: below prevention thresholdRed indicator light: wiring or internal faultYellow indicator light: insulation faultYellow flashing indicator light: communication |
---|
Threshold setting: | Pre-alarm: 1 kOhm...1 MOhmAlarm: 40 Ohm...500 kOhm |
---|
Time delay range: | 0...120 min for signalling circuit |
---|
Response time: | |
---|
[Us] rated supply voltage: | 100...440 V AC 50/60 Hz +/- 15 %100...440 V AC 400 Hz +/- 15 %100...440 V DC +/- 15 % |
---|
Power consumption in VA: | 25 VA |
---|
Measurement voltage: | 120 V15 V33 V |
---|
Measurement current: | 0...3 mA0...825 µA0...375 µA |
---|
Relative impedance: | 40 kOhm - AC at 0.1...440 Hz40 kOhm - DC |
---|
Test function: | ManualSelf test |
---|
Signal contacts composition: | 2 C/O standard or fail-safe |
---|
Signalling circuit voltage: | 250 V - AC at 6 A48 V - DC at 1 A |
---|
Input function: | Injection inhibition: 24 V AC 5 mA |
---|
Communication port protocol: | Modbus |
---|
Communication port support: | RS485 |
---|
Display type: | Digital display |
---|
Mounting mode: | Flush-mounted |
---|
Mounting support: | Panel |
---|
Mounting position: | Horizontal |
---|
Connections - terminals: | Removable screw terminal block0.2...2.5 mm² |
---|
Material: | Thermoplastic |
---|
Overvoltage category: | III |
---|
Product weight: | 0.75 kg |
---|
Cut-out dimensions: | 112 x 148 mm |
---|
Height: | 123 mm |
---|
Width: | 159 mm |
---|
Depth: | 90 mm |
---|
Compatibility code: | IM400 |
---|