Circuit breaker ComPact NSX100F AC/DC, 18kA at 415VAC, TMD trip unit 80A, 2 poles 2d - LV438599
LV438599
This product is no longer available. Contact us for a suitable replacement solution tailored to your needs.
Technical informations
| Range: | ComPact |
|---|---|
| Product name: | ComPact NSX |
| Range of product: | ComPact NSX100...250ComPact NSX100...250 DC |
| Device short name: | NSX100F |
| Product or component type: | Circuit breaker |
| Device application: | Distribution |
| Poles description: | 2P |
| Protected poles description: | 2t |
| [In] rated current: | 80 A at 40 °C |
| [Ue] rated operational voltage: | 690 V AC 50/60 Hz500 V DC |
| Network type: | DCAC |
| Network frequency: | 50/60 Hz |
| Suitability for isolation: | Yes conforming to EN/IEC 60947-2 |
| Utilisation category: | Category A |
| Breaking capacity: | 5Â kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-236Â kA Icu at 250 V DC 1P conforming to IEC 60947-236Â kA Icu at 125 V DC 1P conforming to IEC 60947-236Â kA Icu at 500 V DC 2P conforming to IEC 60947-210Â kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-215Â kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-218Â kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-236Â kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
| Breaking capacity code: | F 18Â kA 415 V AC |
| Trip unit name: | TM-D |
| Trip unit technology: | Thermal-magnetic |
| Control type: | Toggle |
| Mounting mode: | Fixed |
| [Ui] rated insulation voltage: | 750Â V AC 50/60 Hz conforming to IEC 60947-2 |
|---|---|
| [Uimp] rated impulse withstand voltage: | 8Â kV conforming to IEC 60947-2 |
| [Ics] rated service breaking capacity: | 5Â kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-236Â kA at 250 V DC conforming to IEC 60947-236Â kA at 125 V DC conforming to IEC 60947-236Â kA at 500 V DC conforming to IEC 60947-210Â kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-215Â kA at 440 V AC 50/60 Hz conforming to IEC 60947-218Â kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-236Â kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical durability: | 20000Â cycles |
| Electrical durability: | 10000Â cycles at 277 V In20000Â cycles at 277 V In/2 |
| Mounting support: | Backplate |
| Upside connection: | Front |
| Downside connection: | Front |
| Connection pitch: | 35Â mm |
| Protection type: | for overload protection (thermal) for short-circuit protection (magnetic) |
| Trip unit rating: | 80 A at 40 °C |
| Long time pick-up adjustment type Ir: | Fixed |
| Long time pick-up adjustment range: | 1 In |
| Magnetic tripping current: | 640Â A |
| Earth-leakage protection: | Without |
| Width: | 70Â mm |
| Height: | 161Â mm |
| Depth: | 86Â mm |
| Compatibility code: | NSX100 |
In short
Reference LV438599
Product Name Circuit breaker ComPact NSX100F AC/DC, 18kA at 415VAC, TMD trip unit 80A, 2 poles 2d - LV438599
Range Compact
Device function Distribution
Related Categories