9,3/10 out of 1126 reviews
SCHNEIDER

TeSys K control relay - 4 NO - <= 690 V - 24 V DC standard coil - CA3KN40BD

CA3KN40BD

€26.73 Excl. Tax
€32.08 Inc. Tax
available In stock more than 100 units – Dispatched within 24/48h
  • check2 Technical support and dedicated single point of contact
  • check2 Free delivery from 100€ of purchase (Metropolitan France)
  • check2 100% secure payments maestro mastercard paypal visa payplug fintecture alma
Technical informations
Range of product: TeSys K control relay
Range: TeSys
Product name: TeSys CAK
Product or component type: Control relay
Device short name: CA3K
Contactor application: Control circuit
Utilisation category: AC-15DC-13
Pole contact composition: 4 NO
[Ue] rated operational voltage:
Control circuit type: DC standard
[Uc] control circuit voltage: 24 V DC
[Ith] conventional free air thermal current: 10 A (at 50 °C)
Irms rated making capacity: 110 A conforming to IEC 60947
Associated fuse rating: 10 A gG conforming to IEC 6094710 A gG conforming to VDE 0660
[Ui] rated insulation voltage: 690 V conforming to IEC 60947750 V conforming to VDE 0110 group C690 V conforming to BS 5424600 V conforming to CSA C22.2 No 14
Mounting support: PlateRail
Connections - terminals: Screw clamp terminals 1 cable(s) 1.5...4 mm²solidScrew clamp terminals 2 cable(s) 1.5...4 mm²solidScrew clamp terminals 1 cable(s) 0.75...4 mm²flexible with cable endScrew clamp terminals 2 cable(s) 0.75...4 mm²flexible without cable endScrew clamp terminals 1 cable(s) 0.34...1.5 mm²flexible with cable endScrew clamp terminals 2 cable(s) 0.34...1.5 mm²flexible without cable end
Tightening torque: 1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm1.3 N.m - on screw clamp terminals - with screwdriver Philips No 26 mm
Control circuit voltage limits: Operational: 0.8...1.15 Uc (at Drop-out: 0.1...0.75 Uc (at
Operating time: 10 ms coil de-energisation and NO opening30...40 ms coil energisation and NO closing
Mechanical durability: 20 Mcycles
Maximum operating rate: 10000 cyc/h
Immunity to microbreaks: 2 ms
Inrush power in W: 3 W (at 20 °C)
Hold-in power consumption in W: 3 W at 20 °C
Heat dissipation: 3 W
Minimum switching voltage: 17 V
Minimum switching current: 5 mA
Non overlap distance: 0.5 mm
Insulation resistance: > 10 MOhm
Height: 58 mm
Width: 45 mm
Depth: 57 mm
Product weight: 0.225 kg
Compatibility code: CA3K
In short
Reference CA3KN40BD
Product Name TeSys K control relay - 4 NO - <= 690 V - 24 V DC standard coil - CA3KN40BD
Range TeSys
Related Categories