Network frequency: | 50/60 Hz |
---|
Magnetic tripping limit: | 4 x In +/- 20 % |
---|
[Ics] rated service breaking capacity: | 6000 A 100 % x Icu conforming to IEC 60898-1 - 400 V AC 50/60 Hz10 kA 100 % x Icu conforming to IEC 60947-2 - 72...125 V DC10 kA 100 % x Icu conforming to EN 60947-2 - 72...125 V DC6000 A 100 % x Icu conforming to EN 60898-1 - 400 V AC 50/60 Hz4.5 kA 75 % x Icu conforming to IEC 60947-2 - 440 V AC 50/60 Hz15 kA 75 % x Icu conforming to EN 60947-2 - 220...240 V AC 50/60 Hz7.5 kA 75 % x Icu conforming to EN 60947-2 - 380...415 V AC 50/60 Hz4.5 kA 75 % x Icu conforming to EN 60947-2 - 440 V AC 50/60 Hz15 kA 75 % x Icu conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz7.5 kA 75 % x Icu conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz27 kA 75 % x Icu conforming to IEC 60947-2 - 12...133 V AC 50/60 Hz27 kA 75 % x Icu conforming to EN 60947-2 - 12...133 V AC 50/60 Hz |
---|
Limitation class: | 3 conforming to EN 60898-13 conforming to IEC 60898-1 |
---|
[Ui] rated insulation voltage: | 500 V AC 50/60 Hz conforming to IEC 60947-2500 V AC 50/60 Hz conforming to EN 60947-2 |
---|
[Uimp] rated impulse withstand voltage: | 6 kV conforming to EN 60947-26 kV conforming to IEC 60947-2 |
---|
Contact position indicator: | Yes |
---|
Control type: | Toggle |
---|
Local signalling: | Trip indicator |
---|
Mounting mode: | Fixed |
---|
Mounting support: | DIN rail |
---|
Comb busbar and distribution block compatibility: | YES top or bottom |
---|
9 mm pitches: | 4 |
---|
Height: | 85 mm |
---|
Width: | 36 mm |
---|
Depth: | 78.5 mm |
---|
Product weight: | 0.25 kg |
---|
Colour: | White |
---|
Mechanical durability: | 20000 cycles |
---|
Electrical durability: | 10000 cycles |
---|
Connections - terminals: | Single terminal, top or bottom rigid wire(s) 1...25 mm² maxSingle terminal, top or bottom flexible wire(s) 1...16 mm² max |
---|
Wire stripping length: | 14 mm top or bottom |
---|
Tightening torque: | 2 N.m top or bottom |
---|
Earth-leakage protection: | Separate block |
---|